Silent-call Gentex 710ls Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Capteurs Silent-call Gentex 710ls. Silent Call Gentex 710ls User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
710/713CS/LS
7109/7139CS/LS
SERIES
177 Candela Rating (UL1971)
Solid State 90dBA Horn
• Temporal 3 Evacuation Sounding Device (713CS/LS & 7139CS/LS Series)
Nominal 2.5% Sensitivity
5-to-1 Signal-to-Noise Ratio
Full Function Test Switch—Patented Three Position Test
Fully Insect Screened
Quick-Disconnect Wiring Harness (CS Models)
9 VDC Battery Back-Up (7109/7139CS/LS) w/Audible Low Battery Chirp
(Visual Does Not Operate on Battery Back-Up)
Form C Auxiliary Relay Contacts for
Remote Annunciation (CS Models)
T
andem Connection up to 6 Detectors Per System (CS Models)
9 Foot Line Cord (LS Models)
Mounting Hardware
Warranty is 1 Year From Date of Purchase
Dry Contacts Will Activate From the
T
andem Wire
Relays Operate on Battery Back-Up, Visual Does Not Operate
Horn Frequency 3100Hz (Nominal)
Photoelectric Smoke Alarm
with Visual Signaling Appliance
Product Listings
Standard Features
Applications
The 710/713CS/LS and 7109/7139CS/LS
photoelectric single station
smoke alarms are designed to give reliable early warning of the
presence of smoke where both audible and visual alarms are required.
The series features a 90dBA solid state piezo signal and a 177 Candela
strobe with “FIRE” lettering. The strobe is listed per UL 1971.
The 713/7139 Series provides the temporal 3 evacuation tone as a
standard feature. When testing the 713/7139 Series it may take up to 16
seconds longer to go in or out of alarm.
The smoke alarm operates on the light scattering principle, a superior
method of detection in smoldering fires, utilizing a pulsing LED light
source and a photodiode sensor in a fully screened sensing chamber.
Every 4 to 5 seconds the pulsing LED emits an infrared beam that by
passes the photodiode under normal conditions. However, when smoke
enters the sensing chamber, the infrared beam is deflected onto the
sensor by the smoke particles. The LED pulse rate increases to 8 times
the normal rate, and after the photodiode confirms that smoke is present
for 2 consecutive pulses, it will produce the signal necessary to trip an
alarm.
Upon activation, the alarm will emit a 90dBA local audible signal and
activate the high intensity strobe. During the alarm period the strobe will
flash at a brightness of 177 Candela 60 times per minute. After the
smoke has cleared from the detector, the unit will revert to the normal
stand-by condition.
UL 217
CAN/ULC 552-02/553-02 Listed
(710CS & 7109CS Only)
BFP (City of Chicago)
BS+A/MEA
#285-91-E
MSFM Listing #1929
CSFM Listing #7257-569:104 (710/713CS/LS)
CSFM Listing #7257-569:118 (7109/7139CS/LS)
Also UL
1730 listed for Commercial Residential
and Commercial Residential Multiple-station
Smoke Alarms.
NFPA 72
Americans with Disabilities Act (ADA)
Product Compliance
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Photoelectric Smoke Alarm

710/713CS/LS7109/7139CS/LSSERIES• 177 Candela Rating (UL1971)• Solid State 90dBA Horn• Temporal 3 Evacuation Sounding Device (713CS/LS & 7139CS/L

Page 2

NOTES:Candela Rating: 177 Candela UL Listed Strobe Light Flash Rate per Minute : 60 MinimumAvailable in square configuration only.Ceilin

Page 3 - Electrical Specifications

SMOKEDETECTORPOWERAUXILIARYCONTACTSWiring Diagram710CS7109CS713CS7139CS710CS7109CS713CS7139CSHOTNEUTTANDEM11110493RELAY CONTACTSRATED LOAD RESISTIVE0.

Page 4

710/713CS/LS7109/7139CS/LSSERIESGX07905-4Architect & Engineering SpecificationsThe Photoelectric Detector Shall be a Gentex Model 710/713LS/7109/7

Commentaires sur ces manuels